Add to Cart
Specifications | Range | Accuracy |
AC Voltage | 80V/180V | ±(1.0%+5) |
400V/600V | ±(1.0%+5) | |
AC Current | 20A/40A | ±(2%+5) |
100A/200A | ±(2%+5) | |
450A/1000A | ±(2%+5) | |
Active power | 30kW/60kW | ±(3%+5) |
120kW/150kW/300kW/600kW | ±(3%+5) | |
Apparent power | 3kVA/12kVA/30kVA | ±(3%+5) |
120kVA/150kVA/600kVA | ±(3%+5) | |
Reactive Power | 3kVAr/12kVAr/30kVAr | ±(3%+5) |
120kVAr/150kVAr/600kVAr | ±(3%+5) | |
Power Factor | 0.3∽1 | ±(0.02+2) |
Frequency | 30Hz∽1kHz | 0.5%+1 |
Harmonic test | Harmonic number | Precision of harmonic voltage |
45Hz∽65Hz | NO.1 | ±(3.0%+10) |
NO.2-6 | ±(3.5%+10) | |
NO.7-8 | ±(4.5%+10) | |
NO.9-10 | ±(5%+10) | |
NO.11-15 | ±(7%+10) | |
NO.16-20 | ±(10%+10) | |
Feature | ||
Display | 6000counts | |
Data Hold | 100groups | |
Auto Range | √ | |
Data Hold | √ | |
Backlight | √ | |
RS232Interface | √ | |
Low Voltage Indication | √ | |
True RMS | √ | |
General | ||
Power Supply | 4×1.5V AA Batteries | |
Size | 300mm×103mm×51mm | |
Jaw Size | Φ50mm | |
Net weight | 530g(not include batteries) | |
Gross weight | 1478g | |
Safety Rating | EN61010-1 EN61010-2-032, EN61326, CAT Ⅲ. 600V |
Three-phase digital power clamp meter is a handheld aptitude meter with power measurement. Low-consumption high-speed single-chip microprocessor is employed and sophisticated algorithm is applied, as a result, result can be obtained rapidly and precisely, and up to 20 harmonies and distortion value thereof can be measured.
We aim to produce intelligent instruments, provide high quality services, and become an innovative manufacturer.
Our R&D team have over 20 years R&D experience in instrument industry .
Our mission is to get our work done well to become customer’s reliable business friend. S.E.Q( Service , Economic pricing , Quality ) is our concern , we know what you need ,and we know what we have .